PKUS EOx is an electro-optical multiplexer between one G.703/704 E1 and single/dual/quad IEEE C37.94 interface. It connects to relay protection equipment including Line Differential Protection Relays and Teleprotection Units with C37.94 or optical E1 (CMI, G.704) ports to telecom networks via electrical E1 (HDB3, G.704)
Communication channels for relay protection equipment via telecom network
Main functions:
Single (PKUS E01) and dual/quad (PKUS E02) C37.94 or optical E1 to electrical E1 interface converter.
Operating mode: Optical E1/Electrical E1 or C37.94/Electrical E1 (programmable in User Interface Program PKUSConverter).
PKU EO1 features
IEEE Standard Interface C37.94 Nx64 kbps (N=1…12),
Optical interface with SFP transceivers,
Alarm LEDs and contacts,
Compact case (198x115x50 mm), DIN-rail mounting,
Single 48 VDC power supply with two inputs decoupled by diodes,
Integrated nonvolatile and not editable event recorder for alarms and user manipulations with 1 ms time stamps from internal Real Time Clock,
Optional synchronization of Real Time Clock from IRIG-B input,
Upload and text display of all events recorded in PKUS EO1,
All events can be saved to not editable file or COMTRADE file,
IEC 60870-5-101 for SCADA (IEC 60870-5-104 and SNMP with optional external converter),
PKU EO2 features
PKUS EO1/E02 is compatible with any relay protection equipment with C37.94,
Integrated nonvolatile and not editable event recorder,
PKUS EO1/E02 complies with or exceeds the requirements of Russian and international EMC standards,
Immunity against 500 ms power interruptions.
PKUS EO1 | |
Operating mode | C37.94 / Electrical E1 or Optical E1 / Electrical E1 (programmable via PKUSConverter software) |
C37.94 port data rate | Nx64 kbps, N=1…12 (programmable via PKUSConverter software) |
Event recorder | non-volatile, not editable by user |
Size | 198x115x50 mm |
Mounting | DIN-rail |
Power supply | single 48 VDC module with two decoupled diode inputs |
Immunity against power interruptions | 500 ms |
PKUS EO2 | |
Number of converters | two independent 2-channel sub modules |
Operating mode | C37.94 / Electrical E1 or Optical E1 / Electrical E1 (programmable via PKUSConverter software) |
C37.94 port data rate | Nx64 kbps, N=1…12 (programmable via PKUSConverter software) |
Event recorder | non-volatile, not editable by user |
Cross connection functionality | 64 kbps (time slot level) within 2-channel sub module |
Size | 19-inch rack, 1 height unit (1U) |
Power supply | Dual (redundant) 48 VDC, 110 VDC or 220 VAC/VDC (on request) power supply with passive load sharing |
Immunity against power interruptions | 500ms |